Burner Tuning Report Job Name: acme Job Number: 1234 Date: 2026-02-11 Burner Model: xyz Burner Max (mmBTU/hr): 5 Fuel: Natural Gas Air Temp (F): 70 Ambient (psia): 14.7 Air Flow @ Max (SCFM): 950 Air ΔP @ Max ("wc): 29 Gas ΔP @ Max ("wc): 42 Calculated Air Orifice (in): 3.669 Calculated Gas Orifice (in): 0.857 Pos | Gas ΔP | Gas CFH | Air ΔP | Air CFH | A/G ---------------------------------------------- 0% | 0.20 | 345 | 0.20 | 4733 | 13.72 10% | 0.50 | 546 | 0.95 | 10315 | 18.91 20% | 1.20 | 845 | 1.50 | 12961 | 15.33 30% | 1.20 | 845 | 3.60 | 20080 | 23.76 40% | 3.10 | 1358 | 4.40 | 22199 | 16.34